380V Phase Transition Eletrode Boiler Steam Boiler
Operation principle
The electrode phase transition boiler (steam), is a type of electrode boiler which will produce steam through the phase transition inside boiler. The 3PH electrodes are installed in the electrode tube, which is immersed into media water with minimal conductivity. When the electricity is power on, the media water will be quickly heated into media steam with the of electric current. The media steam flows along the first side of heat exchanger (external of heat exchange tube), transfer thermal to the second side of heat exchanger (internal
cold water in heat exchanger tube), turn cold thermal supply water into steam supply. The media steam will be condensed and flow back to media tank to be gasified again, one complete cycle is finished.
Key features
1. Non-spay type
Fully immersed, not inner-outer bushing style. Patent, safer and more stable.
2. Phase transition heat exchange
Structure: boiler with built-in heat exchanger, protected from influence of thermal supply water quality, stable run.
3. Fixed electrode modular
Innovative electrode design, be made of composite materials, and precisely laser positioned. No moving parts, only a small canned pump for adjusting media water level, super reliable.
4. Constant conductivity
Media water phase transition in closed chamber, ensures constant conductivity, no drainage at first side, hence no need conductivity adjusting.
System diagram - electrode phase transition steam boiler
Technical data
Model |
LDR- |
0.25 |
0.5 |
0.6 |
0.75 |
1 |
Steam volume |
kg/h |
250 |
500 |
600 |
750 |
1000 |
Input power |
kW |
189 |
378 |
454 |
567 |
756 |
Steam pressure |
MPa |
0.8 |
Control cabinet power |
kW |
2 |
Thermal transition efficiency |
% |
99 |
Dia. of steam outlet |
DN (mm) |
40 |
40 |
40 |
50 |
50 |
Dia of softened water inlet |
DN |
25 |
Overall dimension |
L (mm) |
2240 |
2240 |
2500 |
2500 |
2500 |
W (mm) |
1310 |
1310 |
1370 |
1500 |
1560 |
H (mm) |
3120 |
3120 |
3300 |
3400 |
3400 |
Shipping weight |
Ton |
1540 |
1585 |
1685 |
2150 |
2350 |
Operation weight |
Ton |
1630 |
1695 |
1810 |
2280 |
2520 |
Notes:Note: 1,drive power: 380V/50Hz/3PH. Boiler be reliable earthed (resistance≤4Ω);One control power source need be provided: AC220V;
2,The main power cable should be available at control room and prepared by client;
3,The electrode boiler is a pure resistive load, no need capacity cabinet for high volt power;
4,The electrode steam generator is a pressure vessel;
5,Definition of model:
Projects